This watts to amps calculator takes watts or kilowatts, works both ways, and also gives the kVA figure, because generators, UPS units and transformers are rated in kVA rather than kW and confusing the two is how equipment gets undersized.
Because kVA is what limits the machine. A generator or transformer is constrained by how much current its windings can carry and how much voltage its insulation can stand, and the product of those two is apparent power in volt-amps. How much real work that current does depends on the load's power factor, which the generator has no control over.
The relationship is simple: kVA = kW ÷ power factor. So a generator rated 100 kVA delivers 80 kW into a load at 0.8, and only 65 kW into a load at 0.65.
| Supply | kW to amps | Amps to kW |
|---|---|---|
| DC | I = kW × 1000 ÷ V | kW = V × I ÷ 1000 |
| Single-phase AC | I = kW × 1000 ÷ (V × PF) | kW = V × I × PF ÷ 1000 |
| Three-phase, line to line | I = kW × 1000 ÷ (√3 × V × PF) | kW = √3 × V × I × PF ÷ 1000 |
The 1000 is just the kilo prefix. Everything else is the same relationship as watts to amps, so if a figure looks wrong by a factor of a thousand, that is where to look first.
The line-to-line voltage, which is the number a three-phase supply is normally quoted at: 400 volts in most of Europe and Australia, 208 or 480 in North America. This calculator assumes line to line.
If you have the line-to-neutral figure instead, 230 volts against 400 for example, the two differ by exactly √3. Using the wrong one puts the answer out by 73%, which is a large enough error to notice but not always large enough to look obviously wrong, which is what makes it dangerous.